The OPC Diagnostics Server provides a means to integrate the Calamp Online RF Diagnostics of the Integra-TR with the end user's OPC/DDE compliant HMI System. Using a tagged format, the information is treated as standard I/O points which can be easily tracked, graphed and archived. You can even bring the data live into MS Excel.

Share on Social Networks

Share Link

Use permanent link to share in social media

Share with a friend

Please login to send this document by email!

Embed in your website

Select page to start with

7. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 4  200 1 - 2013 DCI Technologies Inc. www.dcitech.com Indusoft WebStudio Browsing Window:

21. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 4 - 3  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 7. This Agreement shall be governed by the laws in force in the Province of Alberta, in the country of Canada. NO AC TION AGAINST LICENSOR OR ANY OF ITS DIRECTORS, OFFICERS, EMPLOYEES OR SHAREHOLDERS, REGARDLESS OF FORM (INCLUDING NEGLIGENCE), ARISING OUT OF ANY CLAIMED BREACH OF THIS AGREEMENT OR TRANSACTIONS UNDER THIS AGREEMENT OR IN ANY OTHER WAY RELATED TO THIS AGRE EMENT MAY BE BROUGHT BY CUSTOMER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED. 8. This Agreement contains the entire agreement between the parties with respect to the use, reproduction, and transfer of the enclosed software. 9. The warranty d isclaimer, limitation of liability, and limitation period provisions contained herein shall remain in force and effect after the termination of this Agreement. 10. All questions regarding this Agreement or the license granted herein should be directed to Licensor’s offices at: DCI Technologies Inc. Unit 31, 4948 126 Ave SE Calgary, AB T2Z 0A9 CANADA Ph; 403.720.4885 Fax: 403.720.3905 www.dcitech.com

18. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 3 - 5  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 3.1.4 Telephone You can reach DCI Technologies Inc. by phone between 8:00 AM and 4:00 PM Mountain Standard Time, Monday through Friday excluding Canadian Statutory Holidays. When you call, please be prepared to provide the following inform ation: - Product serial number used for registration - Product name and version number - Type of computer hardware you are using - Software version number of Windows DCI Te chnologies Technical Support: 1.403.720.4885 DCI Technologies Inc. Unit 31, 49 48 126 Ave SE Calgary, AB T2Z 0A9 CANADA Ph; 403.720.4885 Fax: 403.720.3905 www.dcitech.com

8. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 5  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1.3.2 Matrikon OPC Explorer A handy test tool is the Matrikon OPC Explorer. The following screen is a sample of what it looks like when browsi ng for the datapoints from the Dataradio OPC Server. This utility is included on the Installation CD.

6. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 3  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1.3 Connecting your host to the OPC Server 1.3.1 Browsing for Data via OPC The OPC server is browsable, so it is very easy to select the diagnostics data points you want to monitor. For example the following is a screenshot from National Instruments LookOut when browsing for an Integra Diagnostics Datapoint. In this case the highlighted data point is the Receive Signal Strength Indicator for the Radio with a short ID of 100. The listings in most OPC Client Browsers are presented in alphabetical order so common data types are grouped to gether. The Radio Short ID is the last three digits in the datapoint name.

13. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 10  200 1 - 2013 DCI Technologies Inc. www.dcitech.com Inbound connection , which is active only for TCP or TELNET connections, specifies if the OPC Server or the network device is to initiate the TCP or TELNET connection. If cleared, the OPC Server starts the connection. If set, the network dev ice establishes the connection. Accept data from any port , which is active only for UDP connections, specifies if the OPC Server should accept any message sent to the Listen Port or if the message should be validated against the sending Port number. Checki ng this box allows the OPC Server to accept any message. For TELNET connections, there are two additional options. These deal with the placing of NULL characters (hexadecimal 00) after carriage returns (hexadecimal 0D). Some TELNET devices place a NULL aft er a carriage return in binary mode even though the TELNET protocol does not specify this. The first option, Ignore received NULLs after CRs in binary mode, causes The OPC Server to strip all NULLs after carriage returns sent by a TELNET device. The second option, Send NULLs after CRs in binary mode, causes The OPC Server to insert NULLs after any carriage returns it sends to a TELNET device. Usually, you will set both options the same. It is not recommended to use a Telnet connection when connecting to th e Integra Setup Port.

20. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 4 - 2  200 1 - 2013 DCI Technologies Inc. www.dcitech.com Warranty Disclaimer 4. THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OR CONDITIONS, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OR CONDITIONS OF MERCHANTABILITY, MERCHANTABLE QUALITY, DURABILITY, FITNESS FOR A PARTICULAR PURPOSE, AND INFRINGEMENT AND THOSE ARISING BY STATUTE OR OTHERWISE IN LAW OR FROM THE COURSE OF DEALING OR USAGE OF TRADE. LICENSOR DOES NOT WARRANT THAT THE ENCLOS ED SOFTWARE WILL MEET ANY OR ALL OF CUSTOMER’S PARTICULAR REQUIREMENTS, THAT THE ENCLOSED SOFTWARE WILL OPERATE ERROR - FREE OR UNINTERRUPTED OR THAT ALL PROGRAMMING ERRORS IN THE ENCLOSED SOFTWARE CAN BE FOUND IN ORDER TO BE CORRECTED. LICENSOR’S RESPONSIB ILITY TO REPLACE THE DEFECTIVE ENCLOSED SOFTWARE, OR REFUND CUSTOMER’S PAYMENT IS THE SOLE AND EXCLUSIVE REMEDY PROVIDED TO CUSTOMER FOR BREACH OF THIS WARRANTY. Limitation of Liability 5. IN NO EVENT SHALL LICENSOR BE LIABLE UNDER ANY THEORY OF CONTRACT (EVEN IF IN THE NATURE OF A BREACH OF A CONDITION OR A FUNDAMENTAL TERM OR A FUNDAMENTAL BREACH), TORT, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY, INCLUDING NEGLIGENCE, OR MISREPRESENTATION OR ALLEGED INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF THIRD PARTIES, FOR ANY DAMAGES, INCLUDING DIRECT, INDIRECT, SPECIAL, INCIDENTAL, AND CONSEQUENTIAL DAMAGES, EVEN IF CUSTOMER OR SUPPLIER HAS BEEN ADVISED OF THE POSSIBILITY THEREOF INCLUDING LOSS OF DATA, LOSS OF BUSINESS, DOWN - TIME OR FAILURE TO REALI ZE EXPECTED PROFITS OR SAVINGS OR OTHER ECONOMIC OR COMMERCIAL LOSS OF ANY KIND OR FOR ANY CLAIM AGAINST USER BY ANY OTHER PARTY, ARISING IN ANY WAY FROM THIS AGREEMENT OR THE ENCLOSED SOFTWARE, ALL OF WHICH LIABILITY IS HEREBY EXPRESSLY WAIVED. CUSTOMER ACKNOWLEDGES AND AGREES THAT THE WARRANTY DISCLAIMER AND LIMITATION OF LIABILITY PROVISIONS CONTAINED HEREIN ARE REASONABLE GIVEN THAT, AMONG OTHER REASONS, THE ENCLOSED SOFTWARE HAS A RELATIVELY LOW COST. General 6. This Agreement, the License and accom panying documentation, or any part thereof, may not be assigned or transferred by Customer without the prior written consent of Licensor.

19. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 4 - 1  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 4. Warranty and Limited Liability OPC SERVER SOFTWARE LICENSE AGREEMENT DCI TECHNOLOGIES INC. (“LICENSOR”) IS WILLING TO LICENSE THE ENCLOSED SOFTWARE TO YOU (“CU STOMER”) ONLY IF YOU ACCEPT ALL OF THE TERMS AND CONDITIONS OF THIS SOFTWARE LICENSE AGREEMENT. IF YOU DO NOT AGREE TO THESE TERMS AND CONDITIONS, LICENSOR WILL NOT LICENSE THIS SOFTWARE TO YOU, AND IN THAT CASE YOU SHOULD RETURN THIS PRODUCT PROMPTLY, IN CLUDING THE PACKAGING, THE DISK AND PACKAGE, AND ALL WRITTEN MATERIALS TO THE PLACE OF PURCHASE FOR A FULL REFUND. License 1. Licensor hereby grants and Customer hereby accepts a non - exclusive, non - transferable license (the “License”) to use this copy of the enclosed software at one computer workstation at any one time upon the terms and conditions set forth in this agreement. Customer may copy the enclosed software for archival or backup purposes. An additional license is required for use of the enclose d software other than as set out herein. Customer agrees not to modify, merge, reverse engineer, reverse compile, or disassemble the enclosed software, or portions thereof, in any manner whatsoever. Upon modification, merging, reverse engineering, revers e compiling, or disassembling of the enclosed software, or portions thereof, the License is automatically terminated. Term 2. The License is effective upon acceptance by Customer, and shall remain in effect until terminated as provided herein. The Licen se may be terminated by Customer at any time upon written notice to Licensor. Licensor may terminate the License if Customer fails to comply with any term or condition in this agreement. Upon termination by either party, Customer shall return to Licens or, or destroy, the enclosed software and all associated documentation with all copies in any form. Limited Warranty 3. Licensor warrants that the Enclosed software will perform substantially in accordance with the accompanying written documentation for a period of 90 days from the date of Customer’s receipt of the enclosed software.

10. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 7  200 1 - 2013 DCI Technologies Inc. www.dcitech.com T96SR Topic: The Topic Name is the topic name used by client applications. This is the field that would be modified if you were using multi ple communications lines. Create a new topic for each communications line or base station that you need to connect to. The Description field provides a comment for documentation purposes. It has no impact on how the OPC Server operates. The Update Inter val is the number of milliseconds between the times that The OPC Server polls for data from a device for a topic. This is pertinent only for topics with protocols with read messages. If the amount of time required to read data from all topics on a device e xceeds a topic’s update interval, The OPC Server immediately restarts its polling of the topic. If the amount of time is less than the update interval, the OPC Server delays polling the topic for an appropriate period of time. This field is not used in th e Integra Diagnostics so leaving it set to 1000 is fine. The Write Delay is the number of milliseconds that the OPC Server waits before sending a message to a device. This is useful if a device needs a “rest period” between transmissions. For the Integra a delay of 0, or no milliseconds is sufficient. The Topic Variable is an optional value, such as a station address, assigned to the topic. Its value depends on the assigned protocol. The topic variable is used to populate and verify the topic variable seque nce in a message. The Integra and T96SR protocol s do not require the topic variable; you can leave this blank.

9. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 6  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1.3.3 Connect to EXCEL An other easy way to test if things are working correctly with the Integra - TR radio diagnostics is to use the demo Excel spreadsheet program that was provided on the DCI Technologies Installation CD. A sample spreadsheet called “Integra DDE Diagnostics Ver270.xls” has been included to enable you to get some data back i nto Excel from the OPC server. 1.4 Configuring Multiple Device Connection s 1.4.1 Define Topics A topic in the OPC Server is used by client applications to identify groupings of diagnostics data. In the previous screenshot the Topic Name would be “IntegraDiag”. This is the default name that the OPC server uses for the Integra Diagno stics. You can see it listed under the “OPClient1” object in the left pane of the previous window. If you are running multiple radio hub sites and want to gather diagnostics data from more than one hub you will need to create a new topic for each one. Th is is done by stopping the OPC server (click the red traffic light) and then from the menu select “Configure” and click on “Topics”. You will then be presented with a list of current “Topics” and you can choose to modify or create a new one. Once you ha ve made your selecti on the Topic Definition Dialog will allow the specification of a topic. Integra - TR Topic:

11. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 8  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1.4.2 Select Protocol and Configure Device Connections 1.4.2.1 Protocol Selection The Protocol and Devices dropdown lists show the currently assigned protocol and devices for the specific Topic you have selected. The corresponding dropdown list assign s the protocol and dev ices to the Topic. In both cases, The OPC Server presents a list of choices. You can choose only one protocol. Click on “INTEGRA” for the Ca lamp/ D ataradio Integra family of radio modems or T96SR for the DATARADIO T96SR radio modems. 1.4.2.2 Com Port The “Devices ” button will display the following screen: The Com Port Configuration dialog shows the setting of the currently selected Com Port. The s ettings for the Integra Diagnostics is 9600 Baud, 8 data bits, No parity and 1 stop bit as shown in the following screen shot. Flow control should be set to none.

12. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 9  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1.4.2.3 TCP/IP Socket The Winsock Device Configuration dialog shows the selected TCP/IP connection . Type specifies the TCP/IP protocol to use. This must match the protocol used by the target device. The choices are UDP, TCP, and TELNET. Address is the network address of the device. The address may either be the TCP/IP dot address, such as 100.101.10 2.103, or a host name, as defined by the localhosts file or DNS. The OPC Server validates the address at runtime. You can also validate the address using the Ping button. Port is the TCP/IP port number of the software in the network device. This port numbe r identifies a software service to TCP/IP. The OPC Server communicates with this software agent in the network device. If Inbound connection is not checked, you must enter that software’s port number in this field. If Accept data from any port is checked, this field is disabled. Listen Port identifies the OPC Server’s TCP/IP port number. This is required for when using the UDP protocol or for inbound TCP and TELNET connections. Different Winsock devices can use the same listen port. The OPC Server checks wh ere a message came from to determine which device actually sent it. See Accept data from any port for details. Reply Timeout is the amount of time that the OPC Server waits for a reply to a message it has sent a device. This time is in milliseconds. If no response is received within the timeout period, The OPC Server retransmits its message. If another timeout occurs, The OPC Server tries for a third a final time. If there is no response to the third message, The OPC Server declares a communication failure for the device.

4. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 1  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1. OPC Server Installation 1.1 Installing the OPC Server Installing the DATARADIO OPC Server is a three step process. 1. First, install the main OPC server by running “OmniServer_Vxx.exe” from the “OmniServer_INSTALL_FIRST” directory on the CD . You will need to install this prior to implementing anything else. Use the provided codes as contained on your license. 2. The second step is to install the DATARADIO specific Protocol Files by running “Setup.EXE” from the “Dataradio_Protocol_Fi les” directory on the CD. Use the provided serial number contained on your license. 3. Stop OmniServer and then restart the OmniServer OPC Server . Right click on the Omn iServer Icon on the System Tray and select “ Exit ” as seen in the following images.

17. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 3 - 4  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 3. System Overview Easy to use. The OPC Server uses only dialogs so you can use it yourself. You no longer need the specialists required for other OPC servers. Single interface. You now can focus all your attention on your I/O devices instead of learning the client application interface. The OPC Server is capable of being the single server for a variety of different client applications. Simplifies Tasks. Many toolkits require you to handle the background tasks for scheduling and data st orage. The OPC server does all this for you plus it is a browsable server so you can concentrate on what you want to do with the data instead of the protocol itself. Runtime and Developer Versions. You can choose your level of involvement from purchasin g a bundled runtime syste m for the Integra - TR or T96 SR radios right up to a full developer version that allows you to completely modify decoding schemes and data members. DCI also provides programming support, including custom error detection schemes and i nterfaces to other communication devices and client applications. Contact us for details. 3.1 Technical Support At DCI Technologies, we are working hard to provide you with intuitive technical products. However, should you find yourself with a technical ques tion that you can not answer with the provided tools, please contact our Technical Support Department. We are eager to answer your questions and help get your system running the best way possible. 3.1.1 Email Ask questions and receive detailed answers from Tech nical Support by sending an email message to the account listed below. You must include your product model and serial number in your email message. You will receive a reply by email. Email to: helpdesk t@dcitech.com 3.1.2 Web Stay informed about the latest infor mation by checking out DCI Technologies Web site Web Page: http://www.dcitech.com 3.1.3 Resellers Contact your local reseller who should be able to help you with your questions. For information on re - sellers in your area please email us: Purchase Information: orders@yourdci.com

5. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 1 - 2  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 1.2 Getting Started with the OPC Server 1.2.1 Configure your R adio Addressing The Integra and T96SR Radio’s have a short ID number that is configurable; this number can range from 1 to 254 (up to 1023 on the T96SR’s) Each radio in a particular cell must have a unique Short ID if you want to effectively utilize the d iagnostics capability. To get started make sure that you have your test radios configured for a short ID of 100 and 101. Refer to the DATARADIO INTEGRA or T96SR Service manual for details on how to do this. 1.2.2 Connect your Radio to the OPC Server Using a st raight through serial cable (DB9F to DB9M) connect the “SETUP” port of one Integra to the COM 1 port on the computer that has the OPC server installed. If COM 1 is not available, then you will need to refer to the section Configuring Multiple Device Conne ctions in order to redirect the connection to the appropriate COM port or TCP/IP socket on a terminal server. 1.2.3 Start up the OPC Server Using the Windows “START” Menu look under “ ALL PROGRAMS”, then ‘SOFTWARE TOOLBOX”, then “ OMNISERVER ” and then select “OMNI SERVER CONFIGURATION” . This will start up the OPC server and present a the configuration screen. On this interface you can configure your specific communications ports and other settings required by your specific implementation.

1. DCI Technologies Inc. www.dcitech.com OPC DIAGNOSTICS SERVER TECHNICAL MANUAL INTEGRA and T96SR OPC PROTOCOL S Document No: DCI - OPCTR01 Revision 2 . 0 Creation Date: October 18, 2000 Revision Date: April 23, 2013

2. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 ii  200 1 - 2013 DCI Technologies Inc. www.dcitech.com REVISION NOTES Revision History: Rev. No. Description Date By 1.0 Created – First Draft 18 - Oct - 00 W.E.(Ted) Skinner 1.01 Updated document formatting 11 - May - 01 W.E.(Ted) Skinner 2.0 Updated images and syntax to reflect changes in OmniServer 2.7 23 - Apr - 13 W.E.(Ted)Skinner Revision Notes: APPROVALS Date Date Date

16. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 2 - 3  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 2.2 Operating Syste ms  Microsoft Windows XP, Windows 7  The OPC Server is a true 32 - bit program that realizes improved performance under Microsoft's 32 - bit operating systems 2.3 Application Interface The OPC Server supports a wide range of clients. It can even support multipl e clients using different interfaces at the same time.  Supports OPC UA and OPC DA – OLE for Process Control. The data exchange standard supported by major industrial software providers.  Supports DDE (CF_TEXT) – Supported by almost all windows applications for exchanging data with other programs.  FastDDE – An enhanced version of DDE for improved performance with Wonderware’s InTouch and FactorySuite Products.  AdvanceDDE – Also an enhanced version of DDE for improved performance with Rockwell Software’s RSVie w and GE Fanuc’s CIMPLICITY packages.  Wonderware Suitelink – Uses the I/O driver toolkit to exchange data with Wonderware HMI 2.4 Computer Interface  Serial. Communicate to any device connected to your computer via a COM port. Using either standard or special ized serial cards the OPC server can communicate using RS - 232, RS - 422 or RS - 485  TCP/IP . Communicate to TCP, UDP and Telnet based devices. Provide the capability to communicate to your radio over a LAN using terminal servers.  LPT. Send data to a printer, print event logs etc. 2.5 Partial List of Supported Clients  Indusoft WebStudio  National Instruments LookOut  US Data FactoryLink  Wonderware Intouch and FactorySuite  Intellution iFIX and FIX32  Rockwell Software RS - View  Citect  GE - Fanuc CIMPLICITY  Microsoft Excel , Word, Access and VB

3. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 iii  200 1 - 2013 DCI Technologies Inc. www.dcitech.com TABLE OF CONTENTS 1. OPC Server In stallation ................................ ................................ .......................... 1 - 1 1.1 Installing the OPC Server ................................ ................................ .................. 1 - 1 1.2 Getting Started wi th the OPC Server ................................ ................................ . 1 - 2 1.2.1 Configure your Radio Addressing ................................ ................................ . 1 - 2 1.2.2 Connect your Radio to the OPC Server ................................ ......................... 1 - 2 1.2.3 Start up the OPC Server ................................ ................................ ................. 1 - 2 1.3 Connecting your h ost to the OPC Server ................................ .......................... 1 - 3 1.3.1 Browsing for Data via OPC ................................ ................................ ........... 1 - 3 1.3.2 Matrikon OPC Explorer ................................ ................................ ................. 1 - 5 1.3.3 Connect to EXCEL ................................ ................................ ........................ 1 - 6 1.4 Configuring Multiple Dev ice Connections ................................ ......................... 1 - 6 1.4.1 Define Topics ................................ ................................ ................................ . 1 - 6 1.4.2 Select Protocol and Configure Device Connections ................................ ...... 1 - 8 1.4.2.1 Protocol Selection ................................ ................................ .................. 1 - 8 1.4.2.2 Com Port ................................ ................................ ................................ 1 - 8 1.4.2.3 TCP/IP Socket ................................ ................................ ........................ 1 - 9 2. Tag Name Definitions ................................ ................................ .............................. 2 - 1 2.1 Description of DATARADIO Diagnostics ................................ .......................... 2 - 1 2.1.1 Integra - TR OPC and DDE Diagnostics ................................ ......................... 2 - 1 2.1.2 T96SR OPC and DDE Diagnostics ................................ ................................ 2 - 2 2.2 Operating Systems ................................ ................................ .............................. 2 - 3 2.3 Application Interface ................................ ................................ .......................... 2 - 3 2.4 Computer Interface ................................ ................................ ............................ 2 - 3 2.5 Partial List of Supported Clients ................................ ................................ ........ 2 - 3 3. System Over view ................................ ................................ ................................ ...... 3 - 4 3.1 Technical Support ................................ ................................ .............................. 3 - 4 3.1.1 Email ................................ ................................ ................................ .............. 3 - 4 3.1.2 Web ................................ ................................ ................................ ................ 3 - 4 3.1.3 Resellers ................................ ................................ ................................ ......... 3 - 4 3.1.4 Telephone ................................ ................................ ................................ ....... 3 - 5 4. War ranty and Limited Liability ................................ ................................ ............. 4 - 1

14. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 2 - 1  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 2. Tag Name Definitions 2.1 Description of DATARADIO Diagnostics The diagnostic feature of the Integra provides all the information required to monitor and maintain your communications link. Information such as power, temperature, voltage, signal strength, antenna/feedline condition, and data decode performance is transmitted online with no application interruption and provided continuously at a dedicated diagnostics/set - up port separate from the “Data” port. 2.1.1 Integra - TR OPC and DDE Diagnosti cs The Integra - TR OPC Server provides the individual status of network radio modems while the application is running. The diagnostic information is gathered with each transmission and made available to client applications as outlined in the following table . OPC Data Member Server Name is SWToolbox.OmniServer DDE Syntax Excel Syntax is used for the examples Server name is: osrvdde Parameter Description xxx indicates Radio Short ID Number Temp Temperature in degrees Celsius inside the remote unit's case. IntegraDiag.Temp_STNxxx osrvdde |IntegraDiag!Temp_STNxxx SWB+ Supply voltage to remote unit displayed in tenths of a volt. Indication of battery integrity. IntegraDiag.SWB_STNxxx osrvdde |IntegraDiag!SWB_STNxxx RSSI (Receive Signal Strength Indicator) Indicates how well the local station receives the remote unit's transmission in dBm. IntegraDiag.RSSI_STNxxx osrvdde |IntegraDiag!RSSI_STNxxx Remote RSSI (Remote Receive Signal Strength Indicator) Indicates how well the remote unit receives the local s tation’s transmission in dBm IntegraDiag.RemoteRSSI_STNxxx O srvdde | IntegraDiag!RemoteRSSI_STNxxx Fwd Forward power of remote unit displayed in tenths of a watt. Indicates transmitter integrity. IntegraDiag.FWD_STNxxx Osrvdde | IntegraDiag!FWD_STNxxx Re v Reverse power of remote unit. Indicates antenna and feedline integrity. IntegraDiag.Antenna_STNxxx Osrvdde | IntegraDiag!Antenna_STNxxx Good Number of good data blocks received in the last 15 blocks sent. IntegraDiag.GoodReplys_STNxxx Osrvdde | I ntegraD iag!GOODREPLYS_STNxxx Total Number of total data blocks received. Maximum of 15 blocks. IntegraDiag.Polls_STNxxx Osrvdde | IntegraDiag!POLLS_STNxxx

15. DCI - OPCTR01 Integra OPC Diagnostics TECHNICAL MANUAL April 23, 2013 2 - 2  200 1 - 2013 DCI Technologies Inc. www.dcitech.com 2.1.2 T96SR OPC and DDE Diagnostics The T96SR OPC Server provides the individual status of network radio modem s while the application is running. The diagnostic information is gathered with each transmission and made available to client applications as outlined in the following table. OPC Data Member Server Name is SWToolbox.OmniServer DDE Syntax Excel Syntax is used for the examples Server name is: osrvdde Parameter Description xxx indicates Radio Short ID Number Temp Temperature in degrees Celsius inside the remote unit's case. T96Diag .Temp_STNxxx osrvdde | T96Diag !Temp_STNxxx SWB Supply voltage to remote u nit displayed in tenths of a volt. Indication of battery integrity. T96Diag .SWB_STNxxx osrvdde | T96Diag !SWB_STNxxx RSSI (Receive Signal Strength Indicator) Indicates how well the local station receives the remote unit's transmission in dBm. T96Diag .RSS I_STNxxx osrvdde | T96Diag !RSSI_STNxxx IDFlag I ndicates if the radio ID is larger than 1023 and hence the short ID has been truncated. If the Radio ID is less than or equal to 1023 then this flag is set to zero “0” and the short ID address of the radio mo dem is equal to the full address of the radio modem. (See Micro - CAPP TRX Manual for more details) T96Diag .idflag_STNxxx Osrvdde | T96Diag !idflag_STNxxx FRFlag I ndicates the availability of the next two data fields. If this field is set to a value of “1” then the next two fields, indicating forward are reverse power, are available. If this flag is set to “0” then the values in the next two fields are not valid. (See Micro - CAPP TRX Manual for more details) T96Diag .frflag_STNxxx Osrvdde | T96Diag !frflagI_ST Nxxx Fwd Forward power of remote unit displayed in tenths of a watt. Indicates transmitter integrity. T96Diag .FWD_STNxxx Osrvdde | T96Diag !FWD_STNxxx Rev Reverse power of remote unit. Indicates antenna and feedline integrity. T96Diag .Rev_STNxxx Osrvdde | T96Diag !Rev_STNxxx Quality V alue that is representative of the received signal quality. A value of approximately 200 is best quality. Values decrease as signal quality decreases. T96Diag .Quality_STNxxx Osrvdde | T96Diag !Quality_STNxxx